Basic Info.
Model NO.
cj16/19
Description
Cj19/16 Switch-Over Capacitor Contactor
Current
25,32,43-170A
for Capacitor kvar
12-90kvar
Warranty Time
3 Years
Delivery Time
2 Weeks
Certificate
Ce ,LVD ,ISO9001 Certificate
Service
OEM and ODM
Transport Package
80PCS/CTN, One Piece in One Box
Specification
CE, ROHS, ISO9001
Trademark
BSD
Origin
China, Huangshan
HS Code
8536200000
Production Capacity
100000PCS/Month
Product Description
CJ19/16 Switch-over capacitor contactor
Application of AC contactor |
CJ16/19 is developed by our company on the base of 3TK44 capacitor contactor of Siemens company Germany. It's structure is compact, main circuit composed with resistance on -off switch joint the main circuit is convenience, is nidely used as a contactor in controlling small electric capacitor, the model meaning as right . The contact system of contactor is three-phase main circuit, composed by eight pieces contact block from upside and daminside. There is one contact block was switch on in advance in each main circuit, switch-overressistor only two,the cpacitor group is jointed as triangle, so when resistor switch over circuit was sitchon, every capacitor circuit will connected with resistor. The contacor have two pieces of auxilliary contact block, the function is 2NO, 2NC or 1NO+1NC, this is chosed by user. The mounting of this contactor is very convenience, you can use two pieces of M4 screw make it stable, or can use 35mm Din real mou |
Model | CJ19-25 | CJ19-32 | CJ19-43 | CJ19-63 | CJ19-95 | CJ19-115 | CJ19-150 | CJ19-170 | ||||||
Conventional thermal current (A) | 25 | 32 | 43 | 63 | 108 | 250 | 250 | 250 | ||||||
Rated current(A) AC-6b A | 17 | 25 | 29 | 43 | 74 | 87 | 115 | 130 | ||||||
Controlled capacitor kvar | 230V-250V | 6 | 9 | 10 | 15 | 29 | 35 | 45 | 52 | |||||
400V-450V | 12 | 15 | 20 | 30 | 50 | 60 | 80 | 90 | ||||||
690V | 10 | 15 | 20 | 30 | 45 | 55 | 65 | 75 | ||||||
Capability to restrain surge | 20In | |||||||||||||
Coil | Working voltage Us 50Hz V | 220,380 according to the customer's requirement | ||||||||||||
Operating range | 0.85-1.1 Us | |||||||||||||
Consumed power VA | Start | 115 | 200 | 300 | ||||||||||
holding | 11 | 20 | 22 | |||||||||||
Electrical endurance 104 times | 10 | 8 | 6 | 2 | ||||||||||
Mechanical life 104 times | 100 | 80 | 60 | 20 | ||||||||||
The max operation frequency times/h | 300 | 120 | ||||||||||||
Insulation voltage (V) | 500V | 660V | 1000V | |||||||||||
Auxiliary contact | Convention thermal current (A) | 10 | ||||||||||||
Electrical endurance 104 times | AC-15 | 360VA | 12 | |||||||||||
DC-13 | 33W | 12 | ||||||||||||
The smallest load to connect | 6V x 10 mA | |||||||||||||
Current-limited resistor input time (ms) | 7-9 |