Basic Info.
Model NO.
DAM1-630
Poles Number
3
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification
ISO9001-2000, CE, CB, CCC, Asta, Semko, RoHS
Base
BMC Unflaming Material
Thermal Adjustable
Min:0.7-Max:1in
Magnetic Adjustable
Min:5-Max:10in
Rated Insulation Voltage
1000V
Rated Operation Voltage
400/415V
Outline Dimension
255X140X103.5mm
Transport Package
Carton
Specification
250, 315, 400, 500, 630A
Trademark
CDADA, OEM, ODM
Origin
Shanghai, China
HS Code
8536200000
Production Capacity
10000PCS/Month
Product Description
Introduction
DAM1 series Thermal and magnetic adjustable range of Moulded Case Circuit Breakers are designed and manufactured to world-class standards.Provide overload and short-circuit protection for all applications.The thermal&magnetic elements, adjustable over a wide band,make these MCCBs ideal for any distribution application.
°Wide range:400A to 630A(AC)
°Compact dimensions
°Adjustable thermal setting(70-100%)In.
°Adjustable magnetic setting(5-10times)In.
°Push to trip button provision.
°Separate main and arcing contacts
°Wide range of accessories.
DAM1 series Thermal and magnetic adjustable range of Moulded Case Circuit Breakers are designed and manufactured to world-class standards.Provide overload and short-circuit protection for all applications.The thermal&magnetic elements, adjustable over a wide band,make these MCCBs ideal for any distribution application.
Advantages
°Wide range:400A to 630A(AC)
°Compact dimensions
°Adjustable thermal setting(70-100%)In.
°Adjustable magnetic setting(5-10times)In.
°Push to trip button provision.
°Separate main and arcing contacts
°Wide range of accessories.
Thermal Adjustable Magnetic adjustable Circuit Breakers (TAMA) | ||||||
Model | DAM1-630 | |||||
Breaking Capacity Code | N | S | H | G | ||
Rated Current of Frame size- Inm (A) | 400A | |||||
Rated Current-In(40,50 or 55ºC) (A) | 250 - 315 (350)- 400 - 500 - 630A | |||||
Ui(a.c.) 50-60Hz (V) | 750V | |||||
Ue(a.c.) 50-60Hz(V) | 400/415V | |||||
Number of Pole | 3P /4P | |||||
Icu (KA) | 35 | 50 | 70 | 85 | ||
Ics (KA) | 26.25 | 37.5 | 52.5 | 52.5 | ||
Icm(peak)(KA) | 70/0.25 | 110/0.25 | 154/0.2 | 187/0.2 | ||
Uimp (V) | 8000 | |||||
Dielectric Propery (V) | 3000 | |||||
lonization distance (mm) | ≤60/0 | |||||
Endurance | Total Cycles | 5000 | ||||
Electrical Life | 1000 | |||||
Mechanical Life | 4000 | |||||
Over Current trip | Thermal adjustable | Min:0,7In -Max:1In | ||||
Magnetic adjustable | 5In-10In | |||||
Category (EN 60947-2/IEC 60947-2) | Main circuit | A/B | ||||
Auxiliary circuit | AC-15 | |||||
Under Voltage Release | √ | |||||
Shunt Release | √ | |||||
Auxiliary Contact | √ | |||||
Alarm Contact | √ | |||||
Auxiliary and Alarm Contact | √ | |||||
Handle Operation Mechanism | √ | |||||
Electrical Operastion Mechanism | √ | |||||
DIN clips | - | |||||
Terminal cover | √ | |||||
Phase seperator | √ | |||||
Extention Handle | √ | |||||
W (mm) | 3P | 140 | ||||
4P | 184 | |||||
L (mm) | 3P | 254 | ||||
4P | 254 | |||||
H (mm) | 3P | 103.5 | ||||
4P | 103.5 | |||||
Weight | Fixed version 3P/4P | 5.1/7.1 | ||||
Plug-in version 3P/4P | 6.5/8.5 | |||||
Draw out version 3P/4P | 6.5/8.7 |