Product Description
Scope of application
KNHC Modular Contactor (also known as analog contactors and architectural contactors) are mainly used in power systems with AC 50Hz/60Hz, rated working voltage up to 400V and rated working current up to 100A. They are used as remote switches and control circuits in AC-1 and AC-7a (non-inductive or low-inductive loads, resistance furnaces, household appliances and similar low-inductive loads). It can also be used to control the load of household motor. Modular Contactors cant't be used in break short-circuit currents, so appropriate short-circuit protective appliances (such as small circuit breakers) should be selected when using them. It meets the standard IEC 61095. BCH8 contactor can expand auxiliary control, protection and indication functions. BCH8 Modular Contactor is a kind of control device used for long distance connection and disconnection of inductionless or low inductive load, resistance furnace, household appliances and similar low inductive load, household motor, etc. BCH8 Modular Contactor are mainly used in homes, hotels, apartments, office buildings, public buildings, shopping malls, gymnasiums and other places to achieve automatic control functions.
Normal working conditions
Ambient air temperature: The upper limit of ambient air temperature is + 60ºC and the lower limit is - 5ºC. When the AC contactor is installed in the distribution box, spacers must be assembled on both sides to facilitate heat dissipation. Elevation: The altitude of the installation site shall not exceed 2000m.
Atmospheric Conditions: When the installation temperature is + 60ºC, the relative humidity of the air does not exceed 50%. Higher relative humidity can be allowed at lower temperatures, such as + 20ºC up to 90%. Special measures should be taken for occasional condensation due to temperature changes.
Pollution grade: Grade II.
Installation Category: II.
Installation method: TH35-7.5 type guide rail is used for installation. There is no significant impact and vibration at the installation site. It is installed vertically. The inclination between the installation surface and any direction is not more than 5 degrees.
Main technical parameters
Quota system
A) Eight-hour working system: This working system is the basic working system. The agreed free air heating current Ith of the Modular Contactor is determined by this working system.
Intermittent periodic working system: The operating frequency of the AC contactor is 30 times/h and the load factor is 40%.
Action (operation) condition
In the ambient air temperature range of - 5 +60ºC, when the suction coil of the contactor is applied with a quota to control the power supply voltage Us so as to heat it to a stable state, the contactor should be reliably closed at any voltage in the range of (85%~110%) Us, and released and disconnected between 75% and 20% of the rated control power supply voltage Us.
Product life
Mechanical life: The mechanical life of modular contactor is not less than 1 million times.
Electrical life: The electrical life of analog contactor is not less than 100,000 times.
Specifications | 16A | 20A | 25A | 40A | 63A | 100A | ||
Rated current | AC-7a | 16 | 20 | 25 | 40 | 63 | 100 | |
AC-7b | 6 | 7 | 8.5 | 15 | 20 | 30 | ||
Agreed heating current Ith(A) | 25 | 25 | 25 | 63 | 63 | 100 | ||
Rated insulation voltage Ui(V) | 500 | |||||||
Rated operating voltage Ue(V) | 250V(1P/2P) 400V(3P/4P) | |||||||
Number of main contacts | 1P | 1NO,1NC | ||||||
2P | 1NO1NC,2NO,2NC | |||||||
3P | 3NO,3NC | |||||||
4P | 2NO2NC,3NO1NC,4NO,4NC | |||||||
Control power | AC-7a | 230V | 3.5 | 4.5 | 5.5 | 9 | 14 | 22 |
400V | 6.5 | 8 | 10 | 16 | 25 | 38 | ||
AC-7b | 230V | 1.4 | 1.6 | 2 | 3.5 | 4.5 | 6.5 | |
400V | 2.4 | 2.8 | 3.4 | 6 | 8 | 11 | ||
Electrical life(times) | 10ten thousand | |||||||
Mechanical life(times) | 100ten thousand | |||||||
Maximum number of switching operations per hour | 30 | |||||||
Maximum number of switching operations per day | 100 | |||||||
Quota control power supply voltage Us(V) | AC 24/50Hz AC230/50Hz | |||||||
frequency | 50Hz/60Hz | |||||||
Class of pollution | 2 | |||||||
Rated impulse withstand voltage(Uimp) | 2.5kV(4kV--12/24/48VAV) | |||||||
Protection level (IEC60529) | Contactor body | IP20 | ||||||
Installed in distribution box | Ip40 | |||||||
working temperature | -5ºC~+60ºC | |||||||
Storage temperature | -40ºC~+70ºC | |||||||
Hygrothermal resistance(IEC60068.1) | 2-class(At 55ºC,Relative humidity is 95%) | |||||||
ELSV(Ultra-low Safety Voltage) 12/24/48 VAC | ||||||||
Product control meets the requirements of SELV (Safe Ultra-Low Voltage) |