Basic Info.
Model NO.
CM1
Poles Number
3 Pole;4 Pole
Type
Circuit Breaker
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection
Certification
CE, CCC
Rated Current
63,125,160,200,250,400,630,800,1250,1600A
Dielectric Property
2500,3000V
Rated Current of Frame Size Inm
63,160,200,250L
Rated Current of The N Pole
=in
Rated Insulation Voltage Ui
400,500,690V
Uimp Rated Impulse Withstand Voltage
8000,10000V
Transport Package
Export Packing
Specification
3P, 4P
Trademark
GWIEC
Origin
Wenzhou, Zhejiang, China
HS Code
8536200000
Production Capacity
50000
Product Description
Application
RM1(CM1) series MCCB is mainly used in the circuit of AC 50/60Hz,rated insulating voltage 690V (630 type is 500V),rated working voltage up to 690V,and rated current from 6A-800A in distribution line for distributing power,protecting line,overload,short-circuit and under-voltage protection. It also can be used for infrequently starting of motor for overload,short-circuit and under-voltage protections.
It is small size,high breaking capacity and short arcing (without arcing).
The products can be installed vertically and horizontally.And it have front connection,rear connection and plug-in connection.
The product meets the standards of GB14048.2 and IEC60947-2.
The product meets the standards of GB14048.2 and IEC60947-2.
Normal Working Condition
Altitude: not exceed 2000m
Ambient air temperature:
1) Temperature: -5° C---+ 40° C
2) 24 hours average air temperature shall not exceed + 35° C
3) If the air temperature is more than + 40° C, it need remark the special ordering.
Air conditions:
At mounting site,relative humidity not exceed 50% at the max temperature of +40° C,higher relative humidity is allowable under lower temperature.For example,RH could be 90% at +20° C,special measures should be taken to occurrence of dews.
Pollution grade:Grade 3
Protection Grade: IP20
Circuit Breaker Specification:
Type | Rated current (A) | Number of Poles | Rated insulation voltage(V) | Rated operating voltage(V) | Arcing-Over Distance(mm) | Ultimated short Circuit Breaking Capacity(KA) | Service Short Circuit Breaking Capacity(KA) | Operation performance(time) | |
ON | OFF | ||||||||
RM1-100D | 12.5,16,20,25, 32,40, 50,63, 80, 100 | 3P/4P | 950V | 690V | 0 | 18 | 18 | 1500 | 8500 |
RM1-100N | 25 | 25 | |||||||
RM1-100H | 70 | 70 | |||||||
RM1-160D | 100,125,160,180, 200 | 3P/4P | 950V | 690V | 0 | 25 | 25 | 1500 | 7000 |
RM1-160N | 36 | 35 | |||||||
RM1-160H | 70 | 70 | |||||||
RM1-250D | 160,180,200,225, 250 | 3P/4P | 950V | 690V | 0 | 25 | 25 | 1000 | 4000 |
RM1-250N | 36 | 36 | |||||||
RM1-250H | 70 | 70 | |||||||
RM1-400D | 200,225,250,300, 215, 400 | 3P/4P | 950V | 690V | 0 | 35 | 35 | 1000 | 4000 |
RM1-400N | 45 | 45 | |||||||
RM1-400H | 70 | 70 | |||||||
RM1-630D | 400, 500, 630 | 3P/4P | 950V | 690V | 0 | 75 | 75 |
Circuit Breaker Tripping Characteristics:
Rated current of release (A) | Thermodynamic release | (ambient temp+40) | Operational current of magneticrelease (A) | ||
1.05In(cold state) inoperative time (h)
| 1.I3n 0h(eat state)inoperative time(h) | ||||
In<63 | ≥1 | <1 | 10In±20% | ||
63<In<100 | ≥2 | <2 | 10In±20% | ||
100<In<630 | ≥2 | <2 | 5-10In±20% | ||
Rated current of release (A) | Thermodynamic release(ambient temp+40ºC) | ||||
1.0In (cold state) | 1.20In (heat state) | 1.50In (heat state) | 7.2In (heat state) | Operational current of magnetic release (A) | |
12.5<In<400 | ≥2h | <2h | <4min | 2S<Tp<10s | 12In±20% |