Basic Info.
Model NO.
SRB13-63
Function
Overcurrent Protection
Certification
ISO9001-2000, CE, CB, CCC
Model
Srb5-63
Rated Voltage(V)
230/400 VAC
Rated Frequency
50/60Hz
Number of Poles
1p. 1p+N. 2p, 3p, 3p+N, 4p
Transport Package
240 PCS/Carton
Specification
IEC 60898
Trademark
Long Road/OEM
Origin
China
Production Capacity
10, 000
Product Description
1. MCB Description:
• High breaking capacity and current limiting characteristics;
• Can be installed on standard busbars;
• Dual-function terminals on the upper and lower sides (lift type/open type);
• It can be fixed to the busbar on the upper or lower side;
• With isolation function, it can be used as a main switch;
• Red-green color contact status indicator;
• Wiring terminal guide to prevent wrong wiring;
• 3-position guide rail clip for easy removal from the busbar;
• Complete product specifications;
• Applicable up to 48 V DC
• Rated breaking capacity 6kA in accordance with IEC/EN 60898-1
2. Electrical technical data:
3.Mechanical technical data:
• High breaking capacity and current limiting characteristics;
• Can be installed on standard busbars;
• Dual-function terminals on the upper and lower sides (lift type/open type);
• It can be fixed to the busbar on the upper or lower side;
• With isolation function, it can be used as a main switch;
• Red-green color contact status indicator;
• Wiring terminal guide to prevent wrong wiring;
• 3-position guide rail clip for easy removal from the busbar;
• Complete product specifications;
• Applicable up to 48 V DC
• Rated breaking capacity 6kA in accordance with IEC/EN 60898-1
2. Electrical technical data:
Design according to | IEC/EN 60898-1 |
Characteristic | B, C, D |
Rated voltage | AC 230 / 400V |
DC 48V Single-pole, 2 pole in series: 96VDC | |
Rated frequency | 50/60Hz |
Rated current | 6,10,16,20,25,32,40,50,63A |
Short-circuit breaking capacity(Ics=Icn) | B,C,D curve----6000A |
Number of poles | 1,2, 3, 4 |
Endurance | ≥ 20,000 operations |
Power inlet mode | Upcoming |
Allowable ambient temperature range | -40ºC~75ºC |
3.Mechanical technical data:
Per pole width dimension | 18mm |
Installation method | IEC standard rail 35mm |
Enclosure protection grade | IP20 |
Dual function terminals on both sides | Open type / lift type |
Terminal protection | Finger and hand safe |
Terminal wiring capacity | 1-25 mm² |
Terminal screw tightening torque | 2-2.5 Nm |
Busbar thickness | 0.8-2 mm |
Installation angle | function is independent of position |